Wire Size Calculator
Enter the load current and how the circuit is wired. The calculator applies the 125% continuous load rule, selects a standard breaker from Table 240.6(A), then finds the smallest conductor whose corrected ampacity supports that breaker — including the small-conductor limits in 240.4(D) and the next-size-up allowance in 240.4(B).
Amps the circuit will carry
°C
How wire sizing works in the NEC
There is no single table that says “50 amps equals 6 AWG.” The answer comes from three steps that have to agree with each other.
- Find the load. For a continuous load — one that runs three hours or more — take 125% of the current. A 40 A continuous load becomes 50 A here.
- Pick a standard breaker. Table 240.6(A) lists the allowed ratings. You may not invent a 55 A breaker; you go to the next standard size at or above the load.
- Pick the conductor. From Table 310.16, choose the smallest conductor whose corrected ampacity is at least the breaker rating. Correction for ambient temperature and conductor count changes which row you may use.
Why insulation temperature changes the answer
A 6 AWG copper conductor carries 55 A at 60 °C, 65 A at 75 °C, and 75 A at 90 °C. The metal is identical. What changes is the insulation and, just as important, the terminals it lands on.
NM-B cable is a 90 °C conductor with a 60 °C outer jacket, so 334.80 limits it to the 60 °C column. THHN in conduit is a 90 °C conductor, but most breakers and lugs rated 100 A or less are only listed for 60 °C or 75 °C terminations, so 110.14(C) caps the usable ampacity there. This is why 8 AWG THHN on a 50 A breaker is legal while 8 AWG NM-B is not.
The two exceptions that trip people up
240.4(D) caps overcurrent protection for small conductors: 14 AWG at 15 A, 12 AWG at 20 A, and 10 AWG at 30 A, with narrow exceptions for motor circuits and specific applications. Even if 12 AWG THHN at 90 °C could carry 30 A, you cannot put it on a 30 A breaker for a general-purpose circuit.
240.4(B) does the opposite. If the conductor ampacity lands between standard ratings, the next higher standard rating is permitted up to 800 A. A conductor with 95 A ampacity may be protected at 100 A. The calculator flags each time it uses this rule.
Wire size by circuit rating
These are code minimums with no ambient correction, no bundling, and a 30 °C ambient — the values most tables publish. Voltage drop, long runs, and future load are separate reasons to go larger.
| Circuit | Standard breaker | Copper, 60 °C (NM-B) | Copper, 75 °C (THWN) | Aluminum, 75 °C |
|---|---|---|---|---|
| 15 A | 15 A | 14 AWG | 14 AWG | 12 AWG |
| 20 A | 20 A | 12 AWG | 12 AWG | 10 AWG |
| 30 A | 30 A | 10 AWG | 10 AWG | 8 AWG |
| 40 A | 40 A | 8 AWG | 8 AWG | 8 AWG |
| 50 A | 50 A | 6 AWG | 8 AWG | 6 AWG |
| 60 A | 60 A | 6 AWG | 8 AWG | 6 AWG |
| 70 A | 70 A | 4 AWG | 6 AWG | 4 AWG |
| 80 A | 80 A | 4 AWG | 4 AWG | 3 AWG |
| 100 A | 100 A | 2 AWG | 3 AWG | 2 AWG |
| 125 A | 125 A | 1 AWG | 2 AWG | 1/0 AWG |
| 150 A | 150 A | 1/0 AWG | 1 AWG | 2/0 AWG |
| 200 A | 200 A | 4/0 AWG | 2/0 AWG | 4/0 AWG |
Minimum conductor size per 2023 NEC Table 310.16, assuming three or fewer current-carrying conductors at 30 °C ambient.
Reading the result
The large result is the minimum conductor the code allows under the conditions you entered. If the number looks larger than what you see on a job site, check the wire type selector: NM-B at 60 °C almost always requires one size more than THHN at 75 °C.
The equipment grounding conductor comes from Table 250.122 and is sized to the breaker, not to the conductors. It grows with the overcurrent device, not with the circuit length.
Common questions
What size wire do I need for 50 amps?
6 AWG copper for NM-B cable on a 50 A breaker, or 8 AWG copper THHN in conduit with 75 °C terminals. Aluminum is 4 AWG in cable. The difference is temperature rating: 6 AWG NM-B is limited to 55 A at 60 °C, while 8 AWG THHN reaches 50 A at 75 °C.
What size wire for 100 amps?
3 AWG copper THHN at 75 °C, or 1 AWG copper NM-B at 60 °C. Aluminum at 75 °C is 1 AWG. For a dwelling service, 310.15(B)(7) allows conductors rated at 83% of the service rating, which is why 4 AWG copper is often seen on a 100 A service.
Can I always use the 90 °C column of Table 310.16?
No. The 90 °C ampacity is used for correction and adjustment calculations, but 110.14(C) limits the final ampacity to the temperature rating of the weakest termination — 60 °C for most equipment rated 100 A or less, 75 °C for most modern lugs. The calculator applies that terminal ceiling for you.
Why is the breaker sometimes larger than the wire ampacity?
That is 240.4(B), the next-size-up rule. When a conductor's ampacity falls between two standard breaker sizes, the next higher standard rating may be used as long as it does not exceed 800 A. It does not apply to 14, 12, or 10 AWG, which 240.4(D) caps at 15, 20, and 30 A.
Do I size the wire for the load or for the breaker?
Both, and they must agree. Start with the load: 125% of it for a continuous load, then pick a standard breaker at or above that value, then pick the smallest conductor whose corrected ampacity supports the breaker. If the conductor is smaller than the breaker, 240.4(B) or 240.4(D) decides whether it is legal.