Conduit Fill Chart
Maximum number of THHN or THWN conductors that fit in each trade size at the 40% fill limit for three or more conductors. A dash means the conductor does not fit even as a single conductor.
These tables are calculated from Table 5 conductor areas and Table 4 raceway areas, not copied from a manufacturer chart. Different conductor types have different areas — compact stranded THHN and some XHHW-2 conductors will fit more than the table shows.
EMT — electrical metallic tubing
| Trade size | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 4/0 AWG |
|---|---|---|---|---|---|---|---|---|---|
| 1/2 in | 12 | 9 | 5 | 3 | 1 | 1 | 1 | — | — |
| 3/4 in | 21 | 16 | 10 | 5 | 4 | 2 | 1 | 1 | — |
| 1 in | 35 | 25 | 16 | 9 | 6 | 4 | 2 | 1 | 1 |
| 1-1/4 in | 61 | 44 | 28 | 16 | 11 | 7 | 5 | 3 | 1 |
| 1-1/2 in | 83 | 61 | 38 | 22 | 16 | 9 | 7 | 4 | 1 |
| 2 in | 138 | 100 | 63 | 36 | 26 | 16 | 11 | 7 | 4 |
| 2-1/2 in | 241 | 176 | 111 | 64 | 46 | 28 | 20 | 12 | 7 |
| 3 in | 364 | 266 | 167 | 96 | 69 | 42 | 30 | 19 | 10 |
| 3-1/2 in | 476 | 347 | 218 | 126 | 91 | 56 | 39 | 24 | 14 |
| 4 in | 608 | 443 | 279 | 161 | 116 | 71 | 50 | 31 | 18 |
Maximum THHN/THWN conductors in EMT at 40% fill (2023 NEC Chapter 9, Tables 1, 4, and 5).
PVC Schedule 40
| Trade size | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 4/0 AWG |
|---|---|---|---|---|---|---|---|---|---|
| 1/2 in | 11 | 8 | 5 | 3 | 1 | 1 | 1 | — | — |
| 3/4 in | 20 | 15 | 9 | 5 | 4 | 1 | 1 | 1 | — |
| 1 in | 34 | 25 | 15 | 9 | 6 | 4 | 2 | 1 | 1 |
| 1-1/4 in | 59 | 43 | 27 | 15 | 11 | 7 | 5 | 3 | 1 |
| 1-1/2 in | 81 | 59 | 37 | 21 | 15 | 9 | 6 | 4 | 1 |
| 2 in | 135 | 98 | 62 | 35 | 25 | 15 | 11 | 7 | 4 |
| 2-1/2 in | 193 | 141 | 89 | 51 | 37 | 22 | 16 | 10 | 5 |
| 3 in | 299 | 218 | 137 | 79 | 57 | 35 | 25 | 15 | 8 |
| 3-1/2 in | 401 | 292 | 184 | 106 | 76 | 47 | 33 | 20 | 12 |
| 4 in | 517 | 377 | 237 | 137 | 99 | 60 | 43 | 27 | 15 |
Maximum THHN/THWN conductors in PVC Schedule 40 at 40% fill.
PVC Schedule 80
| Trade size | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 4/0 AWG |
|---|---|---|---|---|---|---|---|---|---|
| 1/2 in | 8 | 6 | 4 | 1 | 1 | 1 | — | — | — |
| 3/4 in | 16 | 12 | 7 | 4 | 3 | 1 | 1 | 1 | — |
| 1 in | 28 | 20 | 13 | 7 | 5 | 3 | 1 | 1 | 1 |
| 1-1/4 in | 51 | 37 | 23 | 13 | 9 | 6 | 4 | 2 | 1 |
| 1-1/2 in | 70 | 51 | 32 | 18 | 13 | 8 | 5 | 3 | 1 |
| 2 in | 118 | 86 | 54 | 31 | 22 | 13 | 9 | 6 | 3 |
| 2-1/2 in | 169 | 123 | 78 | 45 | 32 | 19 | 14 | 8 | 5 |
| 3 in | 265 | 193 | 122 | 70 | 50 | 31 | 22 | 13 | 7 |
| 3-1/2 in | 358 | 261 | 164 | 94 | 68 | 42 | 30 | 18 | 10 |
| 4 in | 464 | 338 | 213 | 123 | 88 | 54 | 38 | 24 | 13 |
PVC 80 has thicker walls than PVC 40, so it holds fewer conductors at the same trade size.
IMC and rigid metal conduit
| Trade size | 14 AWG | 12 AWG | 10 AWG | 8 AWG | 6 AWG | 4 AWG | 2 AWG | 1/0 AWG | 4/0 AWG |
|---|---|---|---|---|---|---|---|---|---|
| 1/2 in | 12 | 9 | 5 | 3 | 1 | 1 | 1 | — | — |
| 3/4 in | 22 | 16 | 10 | 6 | 4 | 2 | 1 | 1 | — |
| 1 in | 36 | 26 | 16 | 9 | 6 | 4 | 3 | 1 | 1 |
| 1-1/4 in | 62 | 45 | 28 | 16 | 12 | 7 | 5 | 3 | 1 |
| 1-1/2 in | 85 | 62 | 39 | 22 | 16 | 10 | 7 | 4 | 1 |
| 2 in | 140 | 102 | 64 | 37 | 26 | 16 | 11 | 7 | 4 |
| 2-1/2 in | 200 | 146 | 92 | 53 | 38 | 23 | 16 | 10 | 6 |
| 3 in | 309 | 225 | 142 | 81 | 59 | 36 | 25 | 16 | 9 |
| 3-1/2 in | 412 | 301 | 189 | 109 | 78 | 48 | 34 | 21 | 12 |
| 4 in | 531 | 387 | 244 | 140 | 101 | 62 | 44 | 27 | 15 |
Maximum THHN/THWN conductors in rigid metal conduit at 40% fill. IMC is slightly larger internally.
Internal area by raceway type
Fill is a ratio of areas. These are the total internal areas from Table 4 that every calculation starts from.
| Trade size | EMT | PVC 40 | PVC 80 | IMC | RMC |
|---|---|---|---|---|---|
| 1/2 in | 0.304 | 0.285 | 0.217 | 0.342 | 0.314 |
| 3/4 in | 0.533 | 0.508 | 0.409 | 0.586 | 0.549 |
| 1 in | 0.864 | 0.832 | 0.688 | 0.959 | 0.887 |
| 1-1/4 in | 1.496 | 1.453 | 1.237 | 1.647 | 1.526 |
| 1-1/2 in | 2.036 | 1.986 | 1.711 | 2.225 | 2.071 |
| 2 in | 3.356 | 3.291 | 2.874 | 3.630 | 3.408 |
| 2-1/2 in | 5.858 | 4.695 | 4.119 | 5.135 | 4.866 |
| 3 in | 8.846 | 7.268 | 6.442 | 7.922 | 7.499 |
| 3-1/2 in | 11.545 | 9.737 | 8.688 | 10.584 | 10.010 |
| 4 in | 14.753 | 12.554 | 11.258 | 13.631 | 12.882 |
Total internal area in square inches, NEC Chapter 9 Table 4.
Reading the chart
The values assume the 40% limit that applies to three or more conductors. If you are checking one conductor, the limit is 53%; for two, it is 31%; for a nipple 24 inches or less, it is 60%. The conduit fill calculator applies the correct limit automatically.
A count of nine 12 AWG THHN conductors in 1/2 inch EMT is the number most electricians memorize. It is correct, and it is also close to the limit — ten conductors would exceed 40%.
Why the chart and the calculator can disagree
Conductor area depends on the specific wire. THHN, THWN-2, XHHW-2, and compact stranded versions of the same size all have different areas. Table 5 lists several; this chart uses the standard THHN/THWN value. When a job is tight, use the actual manufacturer's area.