Voltage Drop Calculator
Enter the voltage, current, conductor size, and one-way distance. The calculator returns volts lost, percent drop, the maximum run length for a 3% and 5% drop, and the smallest conductor that meets your target.
Feet from source to load
Drop = 2 × R × I × L ÷ 1,000, using Chapter 9 Table 8 resistance of 1.98 Ω per 1,000 ft. Voltage drop is a recommendation in the NEC except for specific cases such as fire pumps.
Why voltage drop matters
Every conductor has resistance, and every amp through it loses voltage. A long, undersized run delivers less than nameplate voltage to the load, which makes motors run hotter, lights dim, and electronics misbehave. The NEC treats it as a design issue rather than a safety rule, but it is the reason a 20 A circuit that is code-legal on ampacity can still be a bad installation.
The formula
VD = 2 × R × I × L ÷ 1,000 for single phase, and VD = 1.732 × R × I × L ÷ 1,000 for three phase. R is the conductor resistance in ohms per 1,000 ft from Chapter 9 Table 8, I is the load current, and L is the one-way length. The 2 in the single-phase version is the round trip — out on the hot, back on the neutral.
Percent drop is simply VD ÷ system voltage × 100. The classic separation-of-circuits guidance is 3% on a branch circuit and 5% from the service to the farthest outlet.
Ampacity and voltage drop are different questions
Ampacity asks whether the conductor will overheat. Voltage drop asks whether the load will get enough voltage. A 12 AWG conductor on a 20 A breaker is fine for ampacity at almost any residential length, but past about 45 feet at 120 V it starts losing more than 3%. That is why long feeder runs and detached-garage circuits so often use 10 or 8 AWG on a 20 A breaker.
Maximum one-way distance at 3%
The table shows copper conductors carrying 20 A at 120 V, single phase. Distances scale inversely with current and with voltage — double the voltage and you double the distance for the same percentage.
| Copper size | Drop per 100 ft at 20 A | Max run at 3% | Max run at 5% |
|---|---|---|---|
| 14 AWG | 12.56 V | 29 ft | 48 ft |
| 12 AWG | 7.92 V | 45 ft | 76 ft |
| 10 AWG | 4.96 V | 73 ft | 121 ft |
| 8 AWG | 3.11 V | 116 ft | 193 ft |
| 6 AWG | 1.96 V | 183 ft | 305 ft |
| 4 AWG | 1.23 V | 292 ft | 487 ft |
| 2 AWG | 0.78 V | 464 ft | 773 ft |
| 1/0 AWG | 0.49 V | 738 ft | 1230 ft |
Copper, 120 V single phase, 20 A load, 75 °C resistance from NEC Chapter 9 Table 8.
Reading the result
The badge above the numbers is the practical verdict: under 3% is a good design, 3–5% is acceptable on many feeders, and over 5% means the conductor should go up a size or two. The recommended wire line gives you the smallest standard conductor that meets your target at the current and distance you entered.
If the recommendation is several sizes above the ampacity minimum, the run is long enough that voltage drop, not heat, is driving the design. That is normal for well pumps, detached buildings, and dock or gate circuits.
Common questions
What is the voltage drop formula?
Single phase: VD = 2 × R × I × L ÷ 1,000, where R is ohms per 1,000 ft, I is amps, and L is one-way length in feet. Three phase: VD = 1.732 × R × I × L ÷ 1,000. The factor of 2 accounts for the return path in a single-phase circuit.
Is 3% voltage drop required by the NEC?
Not as a general rule. 210.19(A) Informational Note 4 recommends no more than 3% on a branch circuit and 5% total from the service to the outlet. It becomes mandatory for specific installations such as fire pumps under 695.7. Many engineers and inspectors still treat 3% as the working standard.
How far can I run 12 AWG on a 20 amp circuit?
About 45 feet one-way at 120 V before you reach 3% drop, and about 76 feet before 5%. At 240 V the same conductor reaches roughly twice those distances for the same current. Ampacity allows a much longer run than voltage drop does.
Does voltage drop affect the breaker size?
No. The breaker protects the conductor from overcurrent, which is an ampacity question. Voltage drop is a performance question. You may need to increase the conductor for voltage drop, but that never lets you increase the breaker beyond what 240.4 and 240.6(A) allow.
Why does the calculator use resistance instead of impedance?
For conductors 1/0 and smaller in typical branch circuits, reactance is small and resistance dominates, so the DC resistance from Chapter 9 Table 8 is a good approximation. For large feeders or where the result is close to the limit, use the AC impedance values from Chapter 9 Table 9.