Wire Ampacity Calculator
Ampacity is how much current a conductor can carry continuously without damaging its insulation. Start with the Table 310.16 value, then correct it for the ambient temperature and adjust it for how many current-carrying conductors share the raceway.
°C in the raceway or cable run
In the same raceway or cable
12 AWG copper at 75 °C starts at 25 A. After corrections it carries 25 A, and the 25 A value is what you may use for overcurrent sizing when terminals are rated 75 °C.
What ampacity means
Ampacity is a heat problem. Current through a conductor produces I²R losses, the insulation has a maximum operating temperature, and the ampacity table tells you the current that keeps the conductor at that temperature under standard conditions. Change the conditions and the number changes.
The published values in Table 310.16 assume an ambient of 30 °C and no more than three current-carrying conductors in a raceway or cable. Both assumptions are usually wrong in real work, which is why the table is a starting point rather than an answer.
Step one: ambient temperature correction
Table 310.15(B)(1) gives a multiplier for the ambient temperature at the conductor. A 90 °C conductor in a 50 °C attic uses 0.82; the same conductor in a 60 °C mechanical room uses 0.71. Cold environments get a bonus: below 25 °C the factor goes above 1.0, though most installers never use it.
Step two: conductor bundling adjustment
When conductors share a raceway they heat each other. Table 310.15(C)(1) reduces ampacity as the count rises: 80% at four to six conductors, 70% at seven to nine, 50% at ten to twenty, and lower beyond that. The count is of current-carrying conductors only — equipment grounding conductors do not count.
Step three: the terminal ceiling
Section 110.14(C) is where most calculations go wrong. The ampacity you may use for sizing overcurrent protection is limited by the temperature rating of the terminations. A 90 °C conductor on a 75 °C breaker terminal is a 75 °C conductor for that purpose. The calculator reports both numbers so you can see the difference.
| Copper conductor | 60 °C | 75 °C | 90 °C |
|---|---|---|---|
| 14 AWG | 15 | 20 | 25 |
| 12 AWG | 20 | 25 | 30 |
| 10 AWG | 30 | 35 | 40 |
| 8 AWG | 40 | 50 | 55 |
| 6 AWG | 55 | 65 | 75 |
| 4 AWG | 70 | 85 | 95 |
| 3 AWG | 85 | 100 | 115 |
| 2 AWG | 95 | 115 | 130 |
| 1 AWG | 110 | 130 | 145 |
| 1/0 AWG | 125 | 150 | 170 |
| 2/0 AWG | 145 | 175 | 195 |
| 3/0 AWG | 165 | 200 | 225 |
| 4/0 AWG | 195 | 230 | 260 |
NEC 2023 Table 310.16, three or fewer current-carrying conductors, 30 °C ambient. Values in amperes.
Reading the result
The highlighted value is the usable ampacity after correction, adjustment, and the terminal limit. Use it to size the overcurrent device. The two middle values show how much of the reduction came from temperature and how much came from bundling, so you can tell which one is worth fixing — separating circuits may recover more ampacity than paying for a larger conductor.
Ampacity is not the same as wire size. A conductor with plenty of ampacity can still be too small for voltage drop on a long run, and a conductor with plenty of ampacity can still be illegal to protect at the breaker you want because of 240.4(D).
Common questions
What is the ampacity of 12 AWG wire?
20 A at 60 °C, 25 A at 75 °C, and 30 A at 90 °C for copper, based on Table 310.16 with three or fewer current-carrying conductors at 30 °C ambient. For a 20 A branch circuit, 240.4(D) still caps the breaker at 20 A regardless of the 90 °C value.
How much does ambient temperature reduce ampacity?
At 40 °C the correction factor for a 90 °C conductor is 0.91, at 50 °C it is 0.82, and at 60 °C it is 0.71. A 12 AWG THHN conductor rated 30 A at 90 °C carries about 21 A in a 60 °C attic.
Do I count the neutral as a current-carrying conductor?
Usually not in a 120/240 V single-phase system, and not in a balanced three-phase four-wire wye circuit. It counts when it carries the unbalanced current of a nonlinear load with significant harmonic content, such as fluorescent lighting or switching power supplies, per 310.15(E)(3).
Why is the usable ampacity lower than the adjusted ampacity?
Terminals. Section 110.14(C) limits the conductor ampacity to the temperature rating of the termination. Most equipment rated 100 A or less has 60 °C or 75 °C terminals, so the calculator caps the result there even when the conductor insulation is rated 90 °C.
Does bundling apply inside a cable, or only in conduit?
Table 310.15(C)(1) applies to conductors bundled together, whether in a raceway, a cable, or a bundle of cables. Four to six conductors get 80%, seven to nine get 70%, and ten to twenty get 50%. A single NM-B cable with two current-carrying conductors gets no adjustment.