Breaker Size Calculator
Give the load in amps, watts, or kilowatts and the calculator applies the 125% continuous load rule, snaps to the next standard rating in Table 240.6(A), and reports the minimum conductor and equipment grounding conductor for that breaker.
Not used for amp input
Resistive loads are 1.0
- 240.4(D): 10 AWG copper is limited to 30 A overcurrent protection.
How to size a breaker
A breaker has one job: protect the conductor. That is why the process starts with the load and ends with the wire, and why the breaker you pick must be a standard size that the conductor can support.
- Convert the load to amps. Amps = watts ÷ volts for a resistive load. Motors and electronics need the power factor: amps = watts ÷ (volts × PF).
- Apply 125% for continuous loads. A 40 A EV charger becomes 50 A. Noncontinuous loads stay as they are.
- Pick the next standard size. Table 240.6(A) allows 15, 20, 25, 30, 35, 40, 45, 50, 60, 70, 80, 90, 100, 110, 125, 150, 175, 200, 225, 250, 300, 350, 400, 450, 500, 600, 700, 800, 1000, 1200, 1600, 2000, 2500, 3000, 4000, 5000, and 6000 amps. There is no 55 A breaker.
- Verify the conductor. The wire must carry the breaker rating after temperature correction and bundling adjustment.
Standard breaker sizes
You may not round down. A 41 A load needs a 45 A breaker, not a 40 A one, unless the load is noncontinuous and the conductor is sized differently under the specific article that governs it. The list above is complete — anything not on it is a special-order device and probably not what the code intended.
Breaker size is not wire size
It is tempting to look up “50 amp breaker” and stop at 6 AWG. But the conductor depends on insulation, terminations, ambient temperature, and how many conductors share the raceway. The same 50 A breaker may be legal with 8 AWG THHN in a cool conduit and illegal with 6 AWG NM-B in a hot attic.
Worked examples
These assume a continuous load, copper conductors, and 60 °C terminations — the conservative case. Real equipment nameplates usually govern; use the nameplate rating when it is higher.
| Load | Rated power | Current | Breaker | Min. copper wire | Ground |
|---|---|---|---|---|---|
| Space heater | 1,500 W | 12.5 A | 20 A | 12 AWG | 12 AWG |
| Water heater | 4,500 W | 18.8 A | 25 A | 10 AWG | 10 AWG |
| Clothes dryer | 5,000 W | 20.8 A | 30 A | 10 AWG | 10 AWG |
| EV charger (32 A) | 7,680 W | 32 A | 40 A | 8 AWG | 10 AWG |
| Electric furnace | 14,400 W | 60 A | 80 A | 4 AWG | 8 AWG |
Continuous loads at 125%, standard breaker from 240.6(A), 60 °C copper conductors.
Reading the result
The breaker value is the smallest standard rating at or above the required ampacity. If the calculator had to use 240.4(B) to let the conductor land on that breaker, a note appears under the result — read it before you buy wire, because that allowance does not apply to multioutlet receptacle circuits.
Common questions
What size breaker do I need for a 50 amp circuit?
A 50 A breaker, and the wire has to be rated for it: 6 AWG copper NM-B or 8 AWG copper THHN at 75 °C. The breaker is chosen from the standard ratings in 240.6(A); the conductor is chosen so its ampacity supports the breaker.
Do I multiply the load by 125%?
Only for continuous loads — loads expected to run three hours or more, such as EV chargers, water heaters, and most lighting. 210.20(A) requires the overcurrent device to be at least 125% of the continuous load plus 100% of the noncontinuous load.
Can the breaker be larger than the wire ampacity?
Sometimes. 240.4(B) lets you go to the next standard size above the conductor ampacity, up to 800 A, which is how a conductor rated 95 A ends up on a 100 A breaker. It does not apply to 14, 12, or 10 AWG circuits, which 240.4(D) caps at 15, 20, and 30 A.
Why is the breaker size larger than the device nameplate current?
Breakers protect conductors, not appliances. A 30 A dryer on a 30 A breaker is normal even though it draws less, because the circuit is sized for the appliance's rated load and the breaker is sized for the conductor. Motor circuits are different — they use Article 430 and often have breakers well above the running current.
Do I need a GFCI or AFCI breaker?
For most 15 A and 20 A branch circuits in dwellings, yes. AFCI protection is required by 210.12 for kitchens, bedrooms, living rooms, and similar areas, and GFCI by 210.8 for bathrooms, kitchens, garages, outdoors, and other listed locations. That changes the breaker type, not its ampere rating.