Box Fill Calculator
Pick a box, list the conductors entering it, and the calculator adds up every volume allowance Article 314.16 requires — conductors, grounds, clamps, support fittings, and devices — then compares the total with the box capacity.
From the box manufacturer's label
| Volume allowance | cu in |
|---|---|
| 4 × 14 AWG conductors | 8 |
| Equipment grounding conductor (all count as one) | 2 |
| Cable clamps / connectors | 2 |
| 1 device (yoke or strap × 2) | 4 |
| Total required | 16 |
What box fill protects
A box crowded with conductors is hard to work in and impossible to inspect. Insulation gets nicked during folding, splices have no room to sit flat, and heat has nowhere to go. Article 314.16 sets a minimum cubic-inch volume so the finished box can be closed without crushing anything.
The counting rules
Section 314.16(B) assigns a volume allowance to each item in the box, based on the largest conductor size involved:
- Conductors. Every conductor that enters and terminates or splices inside counts once. Conductors passing straight through count zero.
- Grounds. All equipment grounding conductors together count as one allowance, based on the largest ground present.
- Clamps. One allowance if the box has cable clamps or connectors, based on the largest conductor.
- Support fittings. One allowance for studs, hickeys, or similar fittings inside the box.
- Devices. Each yoke or strap counts as two allowances, based on the largest conductor connected to it.
Volume per conductor
Table 314.16(B) gives the cubic inches each conductor size is worth. These are the numbers the calculator uses.
| Conductor size | Volume per conductor | Device (yoke) allowance |
|---|---|---|
| 14 AWG | 2.00 cu in | 4.00 cu in |
| 12 AWG | 2.25 cu in | 4.50 cu in |
| 10 AWG | 2.50 cu in | 5.00 cu in |
| 8 AWG | 3.00 cu in | 6.00 cu in |
| 6 AWG | 5.00 cu in | 10.00 cu in |
NEC 2023 Table 314.16(B). The device column is two conductor allowances, per 314.16(B)(4).
Reading the result
The breakdown table shows exactly where the cubic inches went, so you can see whether the problem is the conductor count, the devices, or the clamps. If the box is short, the note tells you how many cubic inches you need to add. Going to a deeper box is usually cheaper than adding a second box and another splice.
Box fill and conduit fill are separate checks. A conductor set can pass one and fail the other, because conduit fill is about area inside the raceway and box fill is about volume inside the enclosure.
Common questions
How many 14 AWG wires fit in an 18 cubic inch box?
Seven, once you count everything the code counts. Seven 14 AWG conductors take 14.00 cubic inches, the grounding conductor adds 2.00 as a single allowance, and cable clamps add another 2.00 — exactly 18.00. Without clamps you can fit eight.
Do all the grounding conductors count separately?
No. Under 314.16(B)(5), one or more equipment grounding conductors count as a single volume allowance based on the largest one present. Four 14 AWG grounds still cost you 2.00 cubic inches, not 8.00.
How much volume does a device take?
Each yoke, strap, or device counts as two conductors based on the largest conductor connected to it — 314.16(B)(4). A switch or receptacle on 14 AWG costs 4.00 cubic inches. A two-gang box with two devices costs 8.00.
Do pigtails count toward box fill?
A conductor that both originates and terminates inside the box counts once. A conductor passing through without a splice or termination is not counted under 314.16(B)(1), but conductors entering and stopping inside the box count as one each.
Does the box fill rule apply to old-work and plastic boxes?
Yes. Every box has a cubic-inch capacity marked on it or listed by the manufacturer, and 314.16 applies to all of them. Plastic boxes usually have the volume molded into the back and the allowed conductor count printed on the carton.